Home » Products »

EJA118W Diaphragm SeaLED Differential Pressure Transmitters

Delivery term:The date of payment from buyers deliver within days
  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2017-12-23 11:40

  • Browse the number:

    511

Send an inquiries
+
Xi'an Xinyuan Industrial Equipment Co.,Ltd
Contactaixin:

Contactaixin:

xinyuangongye(Mr.)  

Email:

telephone:

phone:

Area:

Beijing

Address:

Unit3.Building1 ,No.3 Courtyard, pailou Alley Dongguan South Street ,Beilin Distrct,Xi’an ,Shaanxi,CHINA .

Website:

http://www.xyindustrial-instruments.com/ http://xinyuangongye.cqzjjx.com/

+
 EJA118W Diaphragm Sealed Differential Pressure Transmitters

Features :

Diaphragm seals are used to prevent process medium form entering directly into the pressure-sensing

assembly of the differential pressure transmitter, they are connected to the transmitter using capillaries

 filled with fill fluid.

 

Standard Specifications :

 

Measurement Ranges:


Capsule       Measurement Span      Measurement Range

 

M               2.5 to 100 kPa                  -100 to 100 kPa
                                                          {-10000 to 10000 mmH2O}
                 {250 to 10000 mmH2O}


H              25 to 500 kPa                           -500 to 500 kPa
                                                               {-5 to 5 kgf/cm2}
                {0.25 to 5 kgf/cm2}

 

Output Signal “”:
4 to 20 mA DC, 2-wire system with digital communication

 

Failure Alarm:
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more(standard)
Down-scale: -5%, 3.2 mA DC or less
-2.5%, 3.6 mA DC or less (Optional code /F1)
Note: Applicable for Output signal code D and E

 

Supply Voltage “”:
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code /A)
10.5 to 30 V DC for intrinsically safe, Type n, nonincendive,
or non-sparking type
10.5 to 28 V DC for TIIS intrinsically safe type

 

Conditions of Communication Line “”:
Power supply voltage;
16.4 to 42 V DC
Load resistance; See Figure 1.
Note: In case of an intrinsically safe transmitter, external
load resistance includes safety barrier resistance.


Communication distance;
2 km, when CEV polyethylene-insulated
PVC-sheathed control cables are used.
Note: Communication distance varies depends on kind of
cable.


Load capacitance; 0.22 µF of less.
Load inductance; 3.3 mH or less.
Spacing from power line; 15 cm or more.
Input impedance of receiver connected receiving resistance;
10 k or more at 2.4 kHz
(See Optional Specifications for Intrinsically safe type)

 

Technical parameters :

 

 


 

Products show :

 

 

 

Why chose us :